Mechanical Room • Component Detail
Water/Glycol Exchanger
Approach ΔT
Warning5.1°F
Target < 12°F
Primary Flow
On Spec145 GPM
Glycol 30% • Pump A
ΔP Across HX
Watch6.1 psi
Clean baseline: 4.8 psi
Duty
Nominal1.8 MMBTU/h
Last 15 min average
Inlet/Outlet Temps & Approach
Past 30 daysPressure Drop
psiHeat transfer is trending lower than expected.
Approach ΔT tightened to ~5°F over the last week; verify flows
and consider cleaning if ΔP continues rising.
View on plant schematic
Live Sensors
Glycol Inlet / Outlet
138°F / 122°F
Water Inlet / Outlet
80°F / 105°F
Flow Stability (5 min)
±1.2%
Estimated Fouling Factor
0.0017 hr·ft²·°F/Btu
Maintenance & Alerts
Last chemical clean
32 days ago
Next inspection
+13 days
Strainer differential
0.6 psi
Alarm state
None